Waterside, Controls, Chillers deltachill – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 151: Commissioning procedure
![background image](/manuals/370932/151/background.png)
Chillers
DELTACHILL
™
Chillers
151
Installation, Commissioning and Maintenance Manual :7025232 12/ 2013
Commissioning Procedure
Waterside
General water
pipework
Ensure that the system water pipework is clean from debris. If a flush and bypass circuit
is included ensure that the system is flushed prior to water entering the unit.
Water filter fitted
Ensure that the water filter is fitted and clean.
Water flow rate
Check that the design water flow rate is available to the unit. If not available do not turn
unit on.
Waterside pressure
drop
Measure the waterside pressure drop of the unit ensuring that the pump (if fitted) is
operating.
Glycol strength
Check and record the glycol type and strength. Low levels of glycol can cause freeze up
problems when operating at low temperatures or during the unit off state during cold
ambient conditions.
Glycol concentration is measured by use of a Refractometer.
Differential pressure
sensor
Ensure that the differential pressure sensor operates satisfactory; the best way to do this
is to reduce the flow to the Chiller.
From pressure curves determine the design flow rate / pressure drop
Make sure that any effects of glycol in the system are taken into account
(Flowrate and pressure drop).
Input into the controller the reduced pressure drop (kPa) value (Normally 80% of
design flow rate)
Once this value is programmed into the controller the water flowrate can be reduced to
verify that the low flow alarm is activated.
Ensure that the tubes connected to the sensor are insulated.
Pump interlock
Check that the pump interlock is fitted and functioning correctly.
Controls
Controller
Record on the commissioning sheet the controller serial numbers details.
Controller type
Address
Serial number
Bios
Boot
Strategy reference
Controller settings
The following controller settings are to be recorded on the commissioning sheet.
Head pressure differential (bar)
Minimum suction pressure (bar)
Supply water set point (Summer/ Day) (°C)
Supply water set point (Winter/ Night) (°C)
Minimum supply water temperature (°C)