Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual

Page 62

Advertising
background image

DELTACHILL

Chillers

62

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC021SX-06BS00

DCC023SX-04BT00

DCC024SX-06BT00

Unit Data

Nominal Run Amps

(1)

A

144.2

152.5

157.5

Maximum Start Amps

(2)

A

361.1

425.0

430.0

Recommended Mains Fuse Size

A

160

200

200

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

4

6

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

6

4

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1

47.5

47.5

Quantity

3

3

3

Motor Rating

kW

24.0

28.2

28.2

Sump Heater Rating

W

75

130

130

Start Amps (2)

A

260

320

320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

42.8

42.8

Circuit 2 Comp RLA (PFC)

N/A

N/A

N/A

Nominal Run Amps

A

124.5

138.4

143.4

Maximum Start Amps

A

348.0

415.6

420.6

Compressor Nominal Run Amps

A

36.5

42.8

42.8

Recommended Mains Fuse Size

A

160

200

200

Electronic Soft-start

Nominal Run Amps

A

144.2

152.5

157.5

Maximum Start Amps

A

257.1

258.3

263.3

Recommended Mains Fuse

A

160

200

200

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

124.5

138.4

143.4

Maximum Start Amps

A

244.0

287.6

292.6

Compressor Nominal Run Amps

A

36.48

42.78

42.78

Recommended Mains Fuse Size

A

160

200

200

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

6.2

6.2

Unit Nominal Run Amps

A

149.2

158.7

163.7

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

2.2

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.6

8.9

8.9

Unit Nominal Run Amps

A

150.78

161.37

166.37

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

6.3

6.3

Unit Nominal Run Amps

A

148.6

158.8

163.8

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

2.2

3

3

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

8

8

Unit Nominal Run Amps

A

150.5

160.5

165.5

Recommended Mains Fuse Size

A

200

200

200

Motor Rating

kW

3

4

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.