Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Extra Quiet Continued

ELECTRICAL DATA

DCC019DX-04AFK0

DCC020DX-06AFK0

DCC021DX-04AKK0

Unit Data

Nominal Run Amps

(1)

A

123.5

123.5

142.1

Maximum Start Amps

(2)

A

336.0

396.0

324.1

Recommended Mains Fuse Size

A

160

160

160

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

2.5

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

8.8

Motor Rating

kW

1.27

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 47.5

33.0 / 47.5

33.0 / 33.0

Quantity

2 + 1

2 + 1

2 + 2

Motor Rating

kW

18.8 / 28.2

18.8 / 28.2

13.7 / 18.8

Sump Heater Rating

W

131 + 75

130 + 75

75

Start Amps (2)

A

215 / 260

215 / 320

215 / 215

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

28.5

28.5

Circuit 2 Comp RLA (PFC)

42.8

42.8

28.5

Nominal Run Amps

A

109.8

109.8

124.0

Maximum Start Amps

A

387.0

387.0

310.5

Compressor Nominal Run Amps

A

28.5 / 42.8

28.5 / 42.8

28.5 / 28.5

Recommended Mains Fuse Size

A

160

160

160

Electronic Soft-start

Nominal Run Amps

A

123.5

123.5

142.1

Maximum Start Amps

A

232.0

268.0

238.1

Recommended Mains Fuse

A

160

160

160

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

109.8

109.8

124.0

Maximum Start Amps

A

259.0

259.0

224.5

Compressor Nominal Run Amps

A

28.5 / 42.8

28.5 / 42.8

28.5 / 28.5

Recommended Mains Fuse Size

A

160

160

160

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

128.5

128.5

147.1

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.6

6.6

6.6

Unit Nominal Run Amps

A

130.1

130.1

148.7

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

3

3

3

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

4.5

Unit Nominal Run Amps

A

128.0

128.0

146.5

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

2.2

2.2

2.2

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

129.8

129.8

148.4

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

3

3

3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.