Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC027DR-04BLL0

DCC028DR-06BLL0

DCC030DR-06BLM0

Unit Data

Nominal Run Amps

(1)

A

189.4

198.0

206.9

Maximum Start Amps

(2)

A

406.4

415.0

479.4

Recommended Mains Fuse Size

A

200

250

250

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

6

6

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

6

6

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1 / 43.1

43.1 / 43.1

47.5 / 43.1

Quantity

2 + 2

2 + 2

2 + 2

Motor Rating

kW

24.0 / 24.0

24.0 / 24.0

28.2 / 24.0

Sump Heater Rating

W

75

75

130 + 75

Start Amps (2)

A

260 / 260

260 / 260

320 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

36.5

42.8

Circuit 2 Comp RLA (PFC)

36.5

36.5

36.5

Nominal Run Amps

A

163.1

171.7

184.3

Maximum Start Amps

A

386.7

395.3

461.6

Compressor Nominal Run Amps

A

36.5 / 36.5

36.5 / 36.5

42.8 / 36.5

Recommended Mains Fuse Size

A

200

250

250

Electronic Soft-start

Nominal Run Amps

A

189.4

198.0

206.9

Maximum Start Amps

A

302.4

311.0

351.4

Recommended Mains Fuse

A

200

250

250

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

163.1

171.7

184.3

Maximum Start Amps

A

282.7

291.3

333.6

Compressor Nominal Run Amps

A

36.5 / 36.5

36.5 / 36.5

42.8 / 36.5

Recommended Mains Fuse Size

A

200

250

250

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.2

6.2

6.2

Unit Nominal Run Amps

A

195.6

204.2

213.1

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

3

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

198.3

206.9

215.8

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

4

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.0

8.0

11.2

Unit Nominal Run Amps

A

197.4

206.0

218.1

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

4

4

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

200.6

209.2

218.1

Recommended Mains Fuse Size

A

200

250

250

Motor Rating

kW

5.5

5.5

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.