Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Free Cool Chiller Regular Quiet Continued

ELECTRICAL DATA

DCF015DR-04ADF0

DCF016DR-04AJJ0

DCF018DR-04BJK0

Unit Data

Nominal Run Amps

(1)

A

108.6

126.0

138.0

Maximum Start Amps

A

385.5

279.0

320.0

Recommended Mains Fuse Size

A

125

160

160

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1 / 47.5

27.0 / 27.0

27.0 / 33.0

Quantity

1 + 1

4

2 + 2

Motor Rating

kW

24.0 / 28.2

13.7 / 13.7

13.7 / 18.8

Sump Heater Rating

W

75

75

75

Start Amps

A

260 / 320

180 / 180

180 / 215

Type Of Start

Direct on line

Direct on line

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

20.9

20.9

Circuit 2 Comp RLA (PFC)

42.8

20.9

28.5

Nominal Run Amps

A

97.3

101.4

116.7

Maximum Start Amps

A

380.8

260.6

303.2

Compressor Nominal Run Amps

A

36.5 / 42.8

20.9 / 20.9

20.9 / 28.5

Recommended Mains Fuse Size

A

125

160

160

Electronic Soft-start

Nominal Run Amps

A

108.6

126.0

138.0

Maximum Start Amps

A

253.1

207.0

234.0

Recommended Mains Fuse

A

125.0

160.0

160.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

97.3

101.4

116.7

Maximum Start Amps

A

246.5

188.6

217.2

Compressor Nominal Run Amps

A

36.5 / 42.8

20.9 / 20.9

20.9 / 28.5

Recommended Mains Fuse Size

A

125

160

160

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

4

4

4

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

8.9

8.9

8.9

Unit Nominal Run Amps

A

117.5

134.9

146.9

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

4

4

4

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.8

11.8

11.8

Unit Nominal Run Amps

A

120.4

137.8

149.8

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

5.5

5.5

5.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

8

Unit Nominal Run Amps

A

114.9

132.3

146.0

Recommended Mains Fuse Size

A

125

160

160

Motor Rating

kW

3

3

4

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

8

8

11.2

Unit Nominal Run Amps

A

116.6

134.0

149.2

Recommended Mains Fuse Size

A

160

160

160

Motor Rating

kW

4

4

5.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.