DeltaChill Free Cool

Cooling Performance Free Cool


The Freecool potential of the DeltaChill can be determined by the temperature difference of the ambient air and the
return water temperatures. The graphs show a temperature difference and therefore changing Freecool ability.

The cooling capacity is derived by multiplying the total number of fans on the unit by the values of flowrate and capacity.

Example

Return water temperature 15°C
Temperature difference from ambient to return water temperature 10°C
Therefore ambient 5°C

DCF014SR-04AL00 chiller having 4 fans equates to

Cooling capacity

35kW x 4

=

140kW*

Flowrate

2 l/s x 4

=

8 l/s*

*Exact cooling capacity and water flowrate may change for unit given above.