Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Free Cool Chiller Extra Quiet Continued

ELECTRICAL DATA

DCF032DX-08BLM0

DCF035DX-08BMM0

Unit Data

Nominal Run Amps

(1)

A

201.1

210.0

Maximum Start Amps

A

473.6

482.5

Recommended Mains Fuse Size

A

250

250

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

External Trace Heating

Available (fitted by others)

W

500

500

Condenser Fan - Per Fan (AC)

Quantity

8

8

Full Load Amps

A

2.5

2.5

Locked Rotor Amps

A

8.8

8.8

Motor Rating

kW

1.27

1.27

Condenser Fan - Per Fan (EC)

Quantity

8

8

Full Load Amps

A

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

43.1 / 47.5

47.5 / 47.5

Quantity

2 + 2

2 + 2

Motor Rating

kW

24.0 / 28.2

28.2 / 28.2

Sump Heater Rating

W

75 + 130

130

Start Amps

A

260 / 320

320 / 320

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

36.5

42.8

Circuit 2 Comp RLA (PFC)

42.8

42.8

Nominal Run Amps

A

178.5

191.1

Maximum Start Amps

A

455.8

468.4

Compressor Nominal Run Amps

A

36.5 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

Electronic Soft-start

Nominal Run Amps

A

201.1

210.0

Maximum Start Amps

A

345.6

354.5

Recommended Mains Fuse

A

250.0

250.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

178.5

191.1

Maximum Start Amps

A

327.8

340.4

Compressor Nominal Run Amps

A

36.5 / 42.8

42.8 / 42.8

Recommended Mains Fuse Size

A

250

250

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

N/A

N/A

Full Load Amps

A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

Motor Rating

kW

N/A

N/A

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

12

Unit Nominal Run Amps

A

213.1

222.0

Recommended Mains Fuse Size

A

250

250

Motor Rating

kW

5.5

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

Unit Nominal Run Amps

A

215.1

224.0

Recommended Mains Fuse Size

A

250

250

Motor Rating

kW

7.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

Unit Nominal Run Amps

A

212.3

221.2

Recommended Mains Fuse Size

A

250

250

Motor Rating

kW

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

14.8

Unit Nominal Run Amps

A

215.9

224.8

Recommended Mains Fuse Size

A

250

250

Motor Rating

kW

7.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.