Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Installation Data


Interconnecting Wiring

DC

C22

/

DCF

2

2

L1

Mains incoming supply 400V/3PH/50Hz

L2

L3

PE

L4

Separate Permanent Supply 230V/1PH/50Hz

N1

PE

L4

External Trace Heating Connections

N1

240V/500W max

502

Unit Remote On/Off 24VAC

505

502

(1)

Evaporator Water Flow Switch 24VAC

504

500

Remote Setpoint Adjust (0-10VDC)

825

502

(1)

Remote Pump Interlock 24VAC

515

502

Setback Setpoint Temperature switch

516

573

Non-Critical Alarm

Volt Free Common Alarm

574

Volt Free Alarm N/O

575

Volt Free Alarm N/C

576

Critical Alarm

Volt Free Common Alarm

577

Volt Free Alarm N/O

578

Volt Free Alarm N/C

RX-/Tx-



IN

RX+/Tx+



Network Connections In

GND



RX-/Tx-



OUT

RX+/Tx+



Network Connections

GND




CAUTION

(1) MUST be directly wired to the chiller to validate warranty.