Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Troubleshooting

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Waterside

Pump not operating

No power to pump

Check isolator, fuses, MCBs, contactor and
control circuit wiring.

Inverter tripped and does not auto reset (the
microprocessor will try and auto reset 3 times)

Reset inverter drive via microprocessor

No water flow

Strainer blocked

Clean strainer

Pump noisy

Air in water system

Purge air from water system

Pump cavitations

Ensure there is 0.5m NPSH suction head to
avoid cavitations.

Unit not operating due to
water pressure sensor low
limit alarm.

Low flow alarm operating

Check that the low flow pressure variable is
set correctly. If too high the unit may have
nuisance trips.

Low temp limit alarm

Partial blockage in evaporator causing low
flow. The water flow is reduced however the
differential pressure switch still remains
healthy as the pressure would increase.

No heat load on system

Ensure that the water strainer and
evaporator are clean.



Ensure there is design cooling load.

Water/ Glycol freezing up
(crystallizes)

Insufficient glycol/water concentration for
operating temperatures.

Check glycol concentration and add
accordingly.