Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC046DR-08BTT0

DCC048DR-10BTT0

DCC051DR-08BVV0

Unit Data

Nominal Run Amps

(1)

A

319.3

327.9

365.6

Maximum Start Amps

(2)

A

591.9

600.5

577.4

Recommended Mains Fuse Size

A

355

355

400

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

17

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

8

10

8

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

8

10

8

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5 / 47.5

47.5 / 47.5

55.2 / 55.2

Quantity

3 + 3

3 + 3

3 + 3

Motor Rating

kW

28.2 / 28.2

28.2 / 28.2

33.1 / 33.1

Sump Heater Rating

W

130

130

140

Start Amps (2)

A

320 / 320

320 / 320

267 / 267

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

42.8

50.3

Circuit 2 Comp RLA (PFC)

42.8

42.8

50.3

Nominal Run Amps

A

291.1

299.7

336.1

Maximum Start Amps

A

568.3

576.9

552.9

Compressor Nominal Run Amps

A

42.8 / 42.8

42.8 / 42.8

50.3 / 50.3

Recommended Mains Fuse Size

A

355

355

400

Electronic Soft-start

Nominal Run Amps

A

319.34

327.94

365.6

Maximum Start Amps

A

463.85

472.45

470.6

Recommended Mains Fuse

A

355

355

400

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

291.1

299.7

336.1

Maximum Start Amps

A

440.3

448.9

446.1

Compressor Nominal Run Amps

A

42.8 / 42.8

42.8 / 42.8

50.3 / 50.3

Recommended Mains Fuse Size

A

355

355

400

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

12

12

Unit Nominal Run Amps

A

331.34

339.94

377.6

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

5.5

5.5

5.5

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

14

14

14

Unit Nominal Run Amps

A

333.3

341.9

379.6

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

7.5

7.5

7.5

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

11.2

11.2

Unit Nominal Run Amps

A

330.5

339.1

376.8

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

5.5

5.5

5.5

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

14.8

14.8

Unit Nominal Run Amps

A

334.1

342.7

380.4

Recommended Mains Fuse Size

A

355

355

400

Motor Rating

kW

7.5

7.5

7.5

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.