Deltachill ™ chillers, Chillers – Airedale DeltaChill FreeCool 110kW - 1080kW User Manual
Page 26
DELTACHILL
™
Chillers
26
Chillers
Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013
Cooling Performance EC Fans Extra Quiet
Ambient (°C)
25
30
35
40
Model
Vorlauftemperatur
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC022DX-06AKK0
5
228.6
55.2
216.5
60.9
203.6
67.2
190.1
74.1
6
235.8
55.6
223.3
61.2
210.1
67.5
196.2
74.5
7
243.0
55.9
230.2
61.6
216.7
67.8
202.4
74.8
8
250.4
56.3
237.2
61.9
223.3
68.2
208.7
75.1
9
257.8
56.7
244.3
62.3
230.1
68.6
215.1
75.5
10
265.4
57.1
251.6
62.7
237.0
68.9
221.6
75.9
DCC024DX-06BKL0
5
255.8
65.9
241.9
72.2
227.2
79.2
211.4
86.9
6
263.6
66.3
249.4
72.6
234.2
79.6
218.1
87.3
7
271.6
66.7
257.0
73.1
241.4
80.0
224.8
87.7
8
279.7
67.1
264.6
73.5
248.6
80.5
231.6
88.2
9
287.8
67.6
272.4
73.9
256.0
80.9
238.5
88.7
10
296.1
68.1
280.3
74.4
263.5
81.4
245.6
89.1
DCC025DX-08BKL0
5
264.1
63.4
250.6
69.4
236.1
76.1
220.7
83.5
6
272.4
63.7
258.5
69.7
243.6
76.4
227.8
83.8
7
280.8
64.0
266.5
70.1
251.3
76.8
235.0
84.2
8
289.3
64.3
274.7
70.4
259.1
77.1
242.3
84.5
9
298.0
64.7
283.0
70.7
266.9
77.4
249.8
84.9
10
306.8
65.0
291.4
71.1
275.0
77.8
257.4
85.2
DCC027DX-06BLL0
5
280.5
76.4
265.2
83.4
248.7
91.1
231.0
99.5
6
288.9
76.9
273.2
83.9
256.3
91.6
238.1
100.1
7
297.6
77.4
281.4
84.4
264.0
92.1
245.4
100.6
8
306.3
77.9
289.7
84.9
271.8
92.7
252.7
101.2
9
315.2
78.4
298.1
85.5
279.8
93.2
260.1
101.7
10
324.1
78.9
306.6
86.0
287.8
93.8
267.7
102.3
DCC028DX-08BLL0
5
290.3
73.1
275.6
79.8
259.6
87.1
242.4
95.2
6
299.4
73.4
284.2
80.1
267.8
87.5
250.1
95.6
7
308.5
73.8
293.0
80.5
276.1
87.9
257.9
96.1
8
317.9
74.2
301.9
80.9
284.6
88.3
265.9
96.5
9
327.3
74.5
310.9
81.3
293.2
88.7
274.0
96.9
10
337.0
74.9
320.1
81.7
301.9
89.1
282.2
97.3
DCC030DX-06BLM0
5
302.7
84.2
285.7
91.9
267.5
100.3
248.1
109.5
6
311.7
84.9
294.2
92.6
275.5
101.0
255.6
110.2
7
320.8
85.5
302.9
93.2
283.7
101.6
263.2
110.9
8
330.1
86.2
311.6
93.9
291.9
102.3
270.9
111.6
9
339.4
86.8
320.5
94.6
300.2
103.0
278.7
112.3
10
348.9
87.5
329.5
95.3
308.7
103.8
286.6
113.0
DCC031DX-08BLM0
5
314.7
80.0
298.3
87.4
280.6
95.4
261.7
104.2
6
324.4
80.5
307.5
87.9
289.3
95.9
269.9
104.7
7
334.2
81.0
316.9
88.4
298.2
96.4
278.2
105.3
8
344.2
81.5
326.4
88.9
307.2
97.0
286.6
105.8
9
354.3
82.0
336.0
89.4
316.3
97.5
295.2
106.4
10
364.6
82.5
345.8
89.9
325.6
98.0
303.9
106.9
DCC032DX-06BMM0
5
321.7
91.9
303.4
100.2
283.8
109.3
263.0
119.3
6
331.1
92.7
312.2
101.0
292.1
110.1
270.7
120.1
7
340.7
93.5
321.3
101.8
300.6
110.9
278.6
121.0
8
350.3
94.3
330.4
102.6
309.2
111.8
286.6
121.8
9
360.1
95.1
339.6
103.5
317.8
112.6
294.7
122.7
10
370.0
95.9
349.0
104.3
326.6
113.5
302.8
123.6
DCC033DX-08BMM0
5
335.6
86.9
317.8
94.8
298.8
103.5
278.5
113.0
6
345.8
87.5
327.5
95.5
307.9
104.1
287.0
113.7
7
356.2
88.1
337.3
96.1
317.2
104.8
295.7
114.3
8
366.7
88.7
347.3
96.7
326.6
105.4
304.5
115.0
9
377.3
89.3
357.4
97.4
336.2
106.1
313.5
115.7
10
388.1
89.9
367.7
98.0
345.9
106.8
322.6
116.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water
T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x
T)
6
For conditions outside of those quoted please refer to Airedale.