Installation, Commissioning and Maintenance Manual :7025232 12/ 2013

Electrical Data Free Cool Chiller Regular Quiet Continued

ELECTRICAL DATA

DCF025SR-06BT00

DCF013DR-04ACD0

DCF014DR-04ADD0

Unit Data

Nominal Run Amps

(1)

A

169.5

94.1

104.1

Maximum Start Amps

A

442.0

321.1

321.1

Recommended Mains Fuse Size

A

200

125

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

100

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

6

4

4

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

6

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

47.5

33.0 / 43.1

43.1 / 43.1

Quantity

3

1 + 1

1 + 1

Motor Rating

kW

28.2

18.8 / 24.0

24.0 / 24.0

Sump Heater Rating

W

130

75

75

Start Amps

A

320

215 / 260

260 / 260

Type Of Start

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

42.8

28.5

36.5

Circuit 2 Comp RLA (PFC)

N/A

36.5

36.5

Nominal Run Amps

A

155.4

83.0

91.0

Maximum Start Amps

A

432.6

314.5

314.5

Compressor Nominal Run Amps

A

42.8

28.5 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

200

125

125

Electronic Soft-start

Nominal Run Amps

A

169.5

94.1

104.1

Maximum Start Amps

A

314.0

207.0

217.1

Recommended Mains Fuse

A

200.0

125.0

125.0

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

155.4

83.0

91.0

Maximum Start Amps

A

304.6

202.5

210.5

Compressor Nominal Run Amps

A

42.8

28.5 / 36.5

36.5 / 36.5

Recommended Mains Fuse Size

A

200

125

125

Condenser Fan - Per Fan (EC Extra Freecooling)

Quantity

6

4

4

Full Load Amps

A

4.5

4.5

4.5

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.86

2.86

2.86

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

12

6.6

6.6

Unit Nominal Run Amps

A

181.5

100.7

110.7

Recommended Mains Fuse Size

A

200

125

125

Motor Rating

kW

5.5

3

3

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.8

9.8

9.8

Unit Nominal Run Amps

A

181.3

103.9

113.9

Recommended Mains Fuse Size

A

200

125

125

Motor Rating

kW

5.5

4

4

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

11.2

6.3

6.3

Unit Nominal Run Amps

A

180.7

100.4

110.4

Recommended Mains Fuse Size

A

200

125

125

Motor Rating

kW

5.5

3

3

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

14.8

8

8

Unit Nominal Run Amps

A

184.3

102.1

112.1

Recommended Mains Fuse Size

A

200

125

125

Motor Rating

kW

7.5

4

4

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.