DELTACHILL

Chillers

52

Chillers

Installation, Commissioning and Maintenance Manual : 7025232 12 / 2013


Electrical Data Regular Quiet Continued

ELECTRICAL DATA

DCC011DR-04ACC0

DCC013DR-04ACD0

DCC014DR-04ADD0

Unit Data

Nominal Run Amps

(1)

A

83.2

93.3

103.3

Maximum Start Amps

(2)

A

265.2

310.2

320.3

Recommended Mains Fuse Size

A

100

125

125

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Recommended Permanent Fuse Size

A

16

16

16

Permanent Supply

VAC

230 V 1 PH 50 Hz

Max Permanent Incoming Cable Size

mm²

4 mm² terminals

Control Circuit

VAC

24V/230VAC

Evaporator

Pad Heater Rating

W

80

80

80

External Trace Heating

Available (fitted by others)

W

500

500

500

Condenser Fan - Per Fan (AC)

Quantity

4

4

4

Full Load Amps

A

4.3

4.3

4.3

Locked Rotor Amps

A

15

15

15

Motor Rating

kW

2

2

2

Condenser Fan - Per Fan (EC)

Quantity

4

4

4

Full Load Amps

A

3.9

3.9

3.9

Locked Rotor Amps

A

N/A

N/A

N/A

Motor Rating

kW

2.56

2.56

2.56

Compressor - Per Compressor

Nominal Run Amps

A

33.0 / 33.0

43.1 / 33.0

43.1 / 43.1

Quantity

1 + 1

1 + 1

1 + 1

Motor Rating

kW

18.8 / 18.8

24.0 / 18.8

24.0 / 24.0

Sump Heater Rating

W

75

75

75

Start Amps (2)

A

215 / 215

260 / 260

260 / 260

Type Of Start

Direct on line

Direct on line

Direct on line

OPTIONAL EXTRAS

Power Factor Correction

Circuit 1 Comp RLA (PFC)

28.5

36.5

36.5

Circuit 2 Comp RLA (PFC)

28.5

28.5

36.5

Nominal Run Amps

A

74.2

82.2

90.2

Maximum Start Amps

A

260.7

305.7

313.7

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 36.5

Recommended Mains Fuse Size

A

100

125

125

Electronic Soft-start

Nominal Run Amps

A

83.24

93.28

103.32

Maximum Start Amps

A

179.22

206.22

216.26

Recommended Mains Fuse

A

100

125

125

Power Factor Correction & Electronic Soft Start

Nominal Run Amps

A

74.2

82.2

90.2

Maximum Start Amps

A

174.7

201.7

209.7

Compressor Nominal Run Amps

A

28.5 / 28.5

36.5 / 28.5

36.5 / 36.5

Recommended Mains Fuse Size

A

100

125

125

Standard Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

88.2

98.3

108.3

Recommended Mains Fuse Size

A

100

125

125

Motor Rating

kW

2.2

2.2

2.2

Larger Head Pump (Single or Run/Standby)

Pump Full Load Amps

A

5

5

5

Unit Nominal Run Amps

A

88.2

98.3

108.3

Recommended Mains Fuse Size

A

100

125

125

Motor Rating

kW

2.2

2.2

2.2

Standard Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

4.5

4.5

4.5

Unit Nominal Run Amps

A

87.7

97.7

107.8

Recommended Mains Fuse Size

A

100

125

125

Motor Rating

kW

2.2

2.2

2.2

Larger Head Inverter Pump (Single or Run/Standby)

Pump Full Load Amps

A

6.3

6.3

6.3

Unit Nominal Run Amps

A

89.5

99.6

109.6

Recommended Mains Fuse Size

A

100

125

125

Motor Rating

kW

3

3

3

(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.

(2) Starting amps refers to the direct on line connections.