Understanding Controller Data Table Addresses

Because PLC-5, SLC 500, and MicroLogix 1100/1400 controllers are 16-bit
platforms and are used with the 32-bit 20-COMM-E adapter, the data will
be transposed from the least-significant word (LSW) to the most-significant
word (MSW) in the controller.

When the I/O was configured (

Chapter 4

), an available data table address

(N20) was used.

Figure 5.12

shows the entire data file address structure for

this example.

Figure 5.12 Data File Table for Example Ladder Logic Program

Important: The N20:0 data table address in this example is used to set a

control timeout value (in seconds) which determines how long
it will take the adapter to detect a communication loss. Enter a
valid value (1…32767) for N20:0. A value of zero (0) is not
valid, because it disables the timeout and all I/O connections
(Logic Command/Status, Reference/Feedback, and Datalinks)
intended for the drive will not execute. A timeout value of
5…20 seconds is recommended.

Depending on the drive,

Table 5.G

,

Table 5.H

,

Table 5.I

,

Table 5.J

,

Table 5.K

, or

Table 5.L

show the I/O definitions as they relate to the N20

data table addresses in

Figure 5.12

being used in this example.

TIP: When using a drive that has 16-bit Datalinks (PowerFlex 70,
PowerFlex 700, and PowerFlex 700H drives) to transfer a 32-bit parameter,
two contiguous drive Datalink parameters (for example, Data Out A1/A2,
B1/B2, and so forth) are required. To determine if a parameter is a 32-bit
parameter, see the Parameter section in the drive documentation and look
for a

symbol in the ‘No.’ column. (All parameters in PowerFlex 700

Series B drives are 32-bit parameters.) For example, parameter 3 - [Output
Current] in a PowerFlex 70 EC drive is a 32-bit parameter. When using a
drive that has 32-bit Datalinks (PowerFlex 700 VC, PowerFlex 700S, and
PowerFlex 750-Series drives), only one drive Datalink parameter is required
to transfer any parameter.