Instance attributes – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 251

Advertising
background image

EtherNet/IP Objects

C-17

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Instance Attributes

Attribute ID Access Rule Name

Data Type

Description

6

Get

DPI Offline Read Full

STRUCT of:

BOOL[32]

CONTAINER

CONTAINER

CONTAINER

STRING[16]

STRING[4]

WORD

WORD

WORD

WORD

WORD

WORD

WORD

BYTE

BYTE

WORD

WORD

CONTAINER

WORD

WORD

WORD

INT

Descriptor

Offline minimum value

Offline maximum value

Offline default value

Parameter name

Offline parameter units

Online minimum parameter instance

Online maximum parameter instance

Online default parameter instance

Multiple parameter instance

Divisor parameter instance

Base parameter instance

Offset parameter instance

Formula number

Pad byte (always zero)

Help instance

Pad word (always a value of zero)

Parameter value

Multiplier

Divisor

Base

Offset

7

Get

DPI Online Read Full

STRUCT of:

BOOL[32]

CONTAINER

(1)

CONTAINER

CONTAINER

CONTAINER

WORD

WORD

STRING[4]

WORD

WORD

WORD

INT

BYTE[3]

BYTE

STRING[16]

Descriptor (see

page C-19

)

Parameter value

Minimum value

Maximum value

Default value

Next parameter

Previous parameter

Units (for example, Amp, Hz)

Multiplier

(2)

Divisor

(2)

Base

(2)

Offset

(2)

Link (source of the value) (0 = no link)

Always zero (0)

Parameter name

8

Get

DPI Descriptor

BOOL[32]

Descriptor (see

page C-19

)

9

Get/Set

DPI Parameter Value

Various

Parameter value in NVS.

(3)

10

Get/Set

DPI RAM Parameter Value

Various

Parameter value in temporary memory.

Valid only for DPI drives.

11

Get/Set

DPI Link

BYTE[3]

Link (parameter or function block that is the

source of the value) (0 = no link)

12

Get

Help Object Instance

WORD

ID for help text for this parameter

13

Get

DPI Read Basic

STRUCT of:

BOOL[32]

CONTAINER

CONTAINER

CONTAINER

CONTAINER

STRING[16]

STRING[4]

Descriptor (see

page C-19

)

Parameter value

Minimum value

Maximum value

Default value

Parameter name

Units (for example, Amp, Hz)

14

Get

DPI Parameter Name

STRING[16]

Parameter name

15

Get

DPI Parameter Alias

STRING[16]

Customer supplied parameter name.

16

Get

Parameter Processing Error BYTE

0 = No error

1 = Value is less than the minimum

2 = Value is greater than the maximum

Advertising