Instance attributes – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 257

Advertising
background image

EtherNet/IP Objects

C-23

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Instance Attributes

5

Get

Fault Data List

STRUCT of:

BYTE

BYTE

WORD[n]

Number of faults/events in the queue. A ‘0’

indicates the fault queue is empty.

6

Get

Number of Recorded Faults WORD

Number of faults/events in the queue. A ‘0’

indicates the fault queue is empty.

7

Get

Fault Parameter Reference

WORD

Number of faults/events in the queue. A ‘0’

indicates the fault queue is empty.

Attribute ID Access Rule Name

Data Type

Description

Attribute ID Access Rule Name

Data Type

Description

0

Get

Full/All Information

STRUCT of WORD

STRUCT of:

BYTE

BYTE

STRING[16]

STRUCT of:

LWORD

BOOL[16]

WORD

CONTAINER[n]

Fault code

Fault source

DPI port

DPI Device Object

Fault text

Fault time stamp

Timer value (0 = timer not supported)

BOOL[0]: (0 = invalid data, 1 = valid data)

BOOL[1]: (0 = elapsed time, 1 = real time)

BOOL[2…15]: Not used

Reserved

Reserved

1

Get

Basic Information

STRUCT of WORD

STRUCT of:

BYTE

BYTE

STRUCT of:

LWORD

BOOL[16]

Fault code

Fault source

DPI port

DPI Device Object

Fault time stamp

Timer value (0 = timer not supported)

BOOL[0]: (0 = invalid data, 1 = valid data)

BOOL[1]: (0 = elapsed time, 1 = real time)

BOOL[2…15]: Not used

2

Get

International Fault Text

STRINGN

Text describing the fault with support for Unicode.

Advertising