Configuring the I/O

4-17

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

The drive’s New Module screen appears.

5. Edit the following information about the drive and adapter.

6. Under Connection Parameters, edit the following information.

Depending on the size of the drive’s Reference/Feedback and the
number of Datalinks used in your I/O configuration,

Table 4.A

,

Table 4.B

, or

Table 4.C

defines the number of 16-bit words that you

need to enter for the Input Size and Output Size boxes.

Box

Setting

Name

A name to identify the drive and adapter.

Description

Optional – description of the drive/adapter.

Comm Format

Data - INT (This setting formats the data in 16-bit words.)

IP Address

The IP address of the adapter.

Open Module

Properties

When this box is checked, clicking

OK opens additional module properties

screens to further configure the drive/adapter. When unchecked, clicking

OK closes the drive’s New Module screen. For this example, check this box.

Box

Assembly Instance

Size

Input

1 (This value is required.)

The value will vary based on your application

(setting of

Parameters 23 - [DPI I/O Cfg] and 36

- [M-S Output]) and the size (16-bit or 32-bit) of

the Reference/Feedback and Datalinks in the

drive. See

Table 4.A

,

Table 4.B

, or

Table 4.C

on

page 4-18

.

Output

2 (This value is required.)

The value will vary based on your application

(setting of

Parameters 23 - [DPI I/O Cfg] and 35

- [M-S Input]) and the size (16-bit or 32-bit) of

the Reference/Feedback and Datalinks in the

drive. See

Table 4.A

,

Table 4.B

, or

Table 4.C

on

page 4-18

.

Configuration

6 (This value is required.)

0 (This value is required.)