Figure 4.14 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 80

Advertising
background image

4-34

Configuring the I/O

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Figure 4.14 SLC 500 Message Configuration Screens for the Control Timeout

General Tab Box

Setting

This Controller
Communication Command

This setting is unavailable (grayed out) and is established when the message is created in the ladder rung.

Data Table Address

(1)

N20:0. An unused controller data table address containing the control timeout value to be written.

Size in Elements

(2)

1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.

Channel

1. Controller port to which the network is connected.

Target Device (data for adapter/drive)
Message Timeout

5. Message timeout duration in seconds.

Data Table Address

(3)

N42:3. Specific starting address of the destination file in the drive.

MultiHop

Yes. Enables communication to allow network messaging to be routed to the adapter/drive. When ‘Yes’ is

selected, a MultiHop tab appears on the message configuration screen.

MultiHop Tab Box

Setting

To Address

10.91.100.79. The IP address of the adapter connected to the drive.

(1)

For details on data table addresses for this example project, see

Table 5.G

Table 5.J

starting on

page 5-23

.

(2)

For details to determine element size for a specific drive, see

Understanding Controller Data Table Addresses on page 5-22

.

(3)

For details on setting the control timeout value and its function, see

N-Files on page C-10

. The Control Timeout (N42:3) is stored in RAM. If the

20-COMM-E adapter is power cycled, the Control Timeout Message must be re-sent. If the Control Timeout is not changed from a non-zero value, the

control message (

page 4-37

) will error out.

TIP: The Control Timeout (N42:3) must be changed to a non-zero value
(5…20 seconds recommended). If the Control Timeout is not changed from
a non-zero value, the control message (

page 4-37

) will error out. The

Control Timeout is stored in RAM. If the adapter is power cycled, the
Control Timeout Message must be re-sent.