PLC-5 Controller Example

Important: The PLC-5 controller must be Series E (Rev. D.1 or higher) to

support the MultiHop feature that routes messaging to the drive.

After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps needed to
configure a simple EtherNet/IP network (see

Figure 4.5

). In our example, we

will configure a PLC-5/40E controller to communicate with a drive using
Logic Command/Status, Reference/Feedback, and Datalinks over the network.

Figure 4.5 Example PLC-5 Controller EtherNet/IP Network

Configuring Parameters for Network I/O

Because the I/O for the drive is message-based, there is no need to configure
any I/O inside the RSLogix 5 project, version 7.00 or later, until using the
I/O as described in

Chapter 5

.

However, to get the adapter to operate with the I/O created in

Chapter 5

, you

need to configure the adapter to accept the I/O and the drive to point to the
appropriate Datalinks.

1. Set adapter Parameters 23 - [DPI I/O Cfg], 35 - [M-S Input], and 36 -

[M-S Output] to values that meet your application requirements.

For this example, the adapter I/O parameters are set to these values.

2. Reset the adapter (see

Resetting the Adapter on page 3-16

) or power

cycle the drive.

For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, see

Drive and Adapter Parameter

Settings on page 5-21

.

IP Address 10.91.100.80

PLC-5/40E Controller with Embedded Ethernet

IP Address 10.91.100.79

PowerFlex 70 Drive with

20-COMM-E Adapter

Computer with

Ethernet Connection

Ethernet

Switch

TIP: Information for PowerFlex 750-Series drives has been added to this
manual where it is applicable.

Adapter Parameter No.

Setting

23 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

35 - [M-S Input]

xxxx xxxx xxx1 1111

36 - [M-S Output]

xxxx xxxx xxx1 1111