4-10

Configuring the I/O

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

10. On the New Module screen, click the Port Configuration tab.

11. In the Port Configuration tab screen, edit the following information.

12. Click Set to save the Port Configuration information which sets the

corresponding offline Subnet Cfg x and Gateway Cfg x parameters in
the adapter.

13. Click OK on the New Module screen.

The new node (‘My_PowerFlex_70_EC_Drive’ in this example) now
appears under the bridge (‘My_EtherNet_IP_Bridge’ in this example)
in the I/O Configuration folder. If you double-click the Controller Tags,
you will see that module-defined data types and tags have been
automatically created (

Figure 4.2

). Note that all tag names are defined

and Datalinks include the assigned drive parameter name. After you
save and download the configuration, these tags allow you to access the
Input and Output data of the drive via the controller’s ladder logic.

Box

Setting

IP Address

The IP address of the adapter that was already set in the General tab. This

field is not configurable (grayed out).

Subnet Mask

The Subnet Mask configuration setting of the network. This setting must

match the setting of other devices on the network (for example,

255.255.255.0).

Gateway

Address

The Gateway Address configuration setting of the network. This setting must

match the setting of other devices on the network (for example, 10.91.100.1).

Enable BootP

When this box is checked, BOOTP is enabled in the adapter and will ignore

the IP address set in the General tab. When unchecked, the controller uses

the set IP address. This is another method to enable/disable BOOTP in the

adapter. For this example, leave this box unchecked.