Controllogix controller example, Controllogix controller example -2 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 48

Advertising
background image

4-2

Configuring the I/O

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

The Configure Drivers screen reappears with the new driver in the
Configured Drivers list.

7. Click Close to close the Configure Drivers screen.

8. Keep RSLinx running and verify that the computer recognizes the drive.

a. Select Communications > RSWho.

b. In the menu tree, click ‘+’ next to the Ethernet driver.

If the ‘EtherNet/IP driver’ cannot see your drive, as an alternative, use
either the ‘Ethernet devices’ or ‘Remote Devices via Linx Gateway’
RSLinx driver.

ControlLogix Controller

Example

After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps needed to
configure a simple EtherNet/IP network (see

Figure 4.1

). In our example, we

will configure a ControlLogix controller with 1756-ENBT (Series A) bridge
to communicate with a drive using Logic Command/Status, Reference/
Feedback, and 16 Datalinks (8 to read and 8 to write) over the network.

Figure 4.1 Example ControlLogix Controller EtherNet/IP Network

IP Address 10.91.100.80

ControlLogix Controller

with 1756-ENBT Bridge

IP Address 10.91.100.79

PowerFlex 70 Drive with

20-COMM-E Adapter

Computer with

Ethernet Connection

Ethernet

Switch

TIP: Information for PowerFlex 750-Series drives has been added to this
manual where it is applicable.