Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 229

Advertising
background image

Adapter Parameters

B-3

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

21

[Comm Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that I/O communication has

been disrupted. This setting is effective only if I/O

that controls the drive is transmitted through the

adapter. When communication is re-established,

the drive will automatically receive commands over

the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

22

[Idle Flt Action]
Sets the action that the adapter and drive will take

if the adapter detects that the controller is in

program mode or faulted. This setting is effective

only if I/O that controls the drive is transmitted

through the adapter. When the controller is put

back in Run mode, the drive will automatically

receive commands over the network again.

Default:

0 = Fault

Values:

0 = Fault

1 = Stop

2 = Zero Data

3 = Hold Last

4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

23

[DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

24

[DPI I/O Act]
Displays the I/O that the adapter is actively

transmitting. The value of this parameter will

usually be equal to the value of

Parameter 23 -

[DPI I/O Cfg].

Bit Values:

0 = I/O Disabled

1 = I/O Enabled

Type:

Read Only

Parameter
No. Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 21 -

[Comm Flt Action] lets you determine the action of the adapter and connected

drive if I/O communication is disrupted. By default, this parameter faults the

drive. You can set this parameter so that the drive continues to run, however,

precautions should be taken to verify that the setting of this parameter does not

create a risk of injury or equipment damage. When commissioning the drive,

verify that your system responds correctly to various situations (for example, a

disconnected cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 22 - [Idle

Flt Action] lets you determine the action of the adapter and connected drive

when the controller is idle. By default, this parameter faults the drive. You can set

this parameter so that the drive continues to run, however, precautions should

be taken to verify that the setting of this parameter does not create a risk of

injury or equipment damage. When commissioning the drive, verify that your

system responds correctly to various situations (for example, a faulted

controller).

Bit

Definition

Not

Us

ed

Not

Us

ed

Not

Us

ed

D

atali

nk

D

D

atali

nk

C

D

atali

nk

B

D

atali

nk

A

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit

Definition

Not

Used

Not

Used

Not

Used

Data

link

D

Data

link

C

Data

link

B

Data

link

A

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Advertising