Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 231

Advertising
background image

Adapter Parameters

B-5

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

36

[M-S Output]
Sets the Master-Slave output data. This data is

produced by the adapter and consumed by the

Master device (for example, scanner).

Default:

xxx0 0001

Bit Values:

0 = I/O disabled

1 = I/O enabled

Type:

Read/Write

Reset Required: Yes

37

[Ref Adjust]
Sets the percent scale factor for the Reference

received from the network.

Default:

100.00%

Minimum:

0.00%

Maximum:

200.00%

Type:

Read/Write

Reset Required: No

38

39

[Peer A Input]

[Peer B Input]
Sets the destination of the peer I/O input. The

adapter receives this data from the network and

sends it to the drive.
Important: Changes to these parameters are

ignored when

Parameter 47 - [Peer Inp Enable] is

set to ‘1’ (On).
Important: If the parameter is set to input a Logic

Command, configure the mask in

Parameter 40 -

[Peer Cmd Mask] so that the desired bits from the

peer device are used.

Default:

0 = Off

Default:

0 = Off

Values:

0 = Off

1 = Cmd/Ref

2 = Datalink A Input

3 = Datalink B Input

4 = Datalink C Input

5 = Datalink D Input

Type:

Read/Write

Reset Required: No

40

[Peer Cmd Mask]
Sets the mask for the Logic Command word when

it is received through peer input. If the mask bit is

‘0’ (Off), the command bit is ignored and not used.

If the mask bit is ‘1’ (On), the command bit is

checked and used.
Important: If the adapter receives a Logic

Command from both a Master device and a peer

device, each command bit must have only one

source. The source of command bits set to ‘0’ will

be the Master device. The source of command bits

set to ‘1’ will be the peer device.

Default:

0000 0000 0000 0000

Minimum:

0000 0000 0000 0000

Maximum:

1111 1111 1111 1111

Values:

0 = Ignore bit

1 = Check bit

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details

Bit

Definition

No

t Us

ed

No

t Us

ed

No

t Us

ed

Da

tali

nk

D Output

Da

tali

nk

C Output

D

atali

nk

B

O

utpu

t

D

atali

nk

A

O

utpu

t

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

!

ATTENTION: To guard against equipment damage and/or personal injury, note

that changes to

Parameter 37 - [Ref Adjust] take effect immediately. A drive

receiving its Reference from the adapter will receive the newly scaled

Reference, resulting in a change of speed.

Advertising