Dpi alarm object, Class code, Services – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 258: Instances, Class attributes, C-24

Advertising
background image

C-24

EtherNet/IP Objects

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

DPI Alarm Object

Class Code

Products such as PowerFlex drives use this object for alarms or warnings.
Adapters do not support this object.

Services

Instances

The number of instances depends on the maximum number of alarms
supported by the queue. The maximum number of alarms can be read in
Instance 0, Attribute 2.

Class Attributes

Hexadecimal Decimal
0x98

152

Service Code Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Instances (Hex.) (Dec.)

Device

Example

Description

0x0000…0x3FFF 0…16383 Host

0

Class Attributes (Drive)

Only host devices can have alarms.

1

Most Recent Alarm

2

Second Most Recent Alarm

Attribute ID Access Rule Name

Data Type

Description

1

Get

Class Revision

WORD

Revision of object

2

Get

Number of Instances

WORD

Maximum number of alarms that the

device can record in its queue

3

Set

Alarm Command Write

BYTE

0 = No Operation

1 = Clear Alarm

2 = Clear Alarm Queue

3 = Reset Device

4

Get

Fault Data List

STRUCT of:

BYTE

BYTE

WORD[n]

Reserved

5

Get

Number of Recorded Alarms

WORD

Number of alarms in the queue. A ‘0’

indicates the alarm queue is empty.

Advertising