Using Explicit Messaging

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

SLC 500 Controller Explicit Messaging Using the Read/Write Parameter

Service

SLC 500 Controller Example Ladder Logic Program to Read a Single Parameter

A Read Parameter message is used to read a single parameter. This read
message example reads the value of parameter 003 - [Output Current] in a
PowerFlex 7-Class drive.

Important: Parameter Object Class code 0x0F is not supported in

PowerFlex 750-Series drives. To do a single parameter read,
follow the SLC 500 (Generic Attribute Service) single read
example on

page 6-36

.

Figure 6.34 Example Ladder Logic to Read a Single Parameter