Configuring the I/O

4-5

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

There are three ways to add the adapter into the I/O configuration:

• Drive Add-on Profiles (RSLogix 5000 software, version 16.00 or later)

• Classic Profile (RSLogix 5000 software, versions 13.00…15.00)

• Generic Profile (RSLogix 5000 software, all versions)

These are described in separate sections below. If your version of RSLogix
5000 software supports drive Add-on Profiles, we recommend that you use
this method.

Using RSLogix 5000 Drive Add-on Profiles, Version 16.00 or Later

When compared to using the RSLogix 5000 Classic Profile (versions
13.00…15.00) or Generic Profile (all versions), the RSLogix 5000 drive
Add-on Profiles provide the following advantages:

• Profiles for specific drives that provide descriptive controller tags for

basic control I/O words (Logic Command/Status and Reference/
Feedback) and Datalinks. Additionally, Datalinks automatically take the
name of the drive parameter to which they are assigned. These profiles
virtually eliminate I/O mismatch errors and substantially reduce drive
configuration time.

• New Drive tab eliminates the need for a separate drive software

configuration tool.

• Drive configuration settings are saved as part of the RSLogix 5000

software, version 16.00 or later, project file (.ACD) and also downloaded
to the controller.

• Unicast connection (requires RSLogix 5000 software, version 18.00 or

later, and 20-COMM-E Series B adapter firmware 4.001 or later)

• Drive Add-on Profiles can be updated anytime. When a new drive is

used, or to benefit from new updates for Add-on Profiles, you will need
the newest Add-on Profile update. Go to

http://www.ab.com/support/

abdrives/webupdate

to download the latest RSLogix 5000 drive Add-on

Profile. To determine your drive Add-on Profile version, see
Allen-Bradley Knowledgebase document #65882.

Add the Drive/Adapter to the I/O Configuration

To transmit data between the bridge and the drive, you must add the drive as
a child device to the parent bridge. In this example, RSLogix 5000 software,
version 16.00 is used with drive Add-on Profile version 3.01.

1. In the treeview, right-click on the bridge and choose New Module… to

display the Select Module screen.