Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 184

Advertising
background image

6-58

Using Explicit Messaging

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

MicroLogix 1100/1400 Controller – Formatting a Message to Write a Single
Parameter Using Read/Write Parameter Service

Figure 6.71 Write Parameter Message Configuration Screens

The following table identifies the data that is required in each box to
configure a message to write a single parameter.

General Tab

Example Value

Description

Channel

Comm… Command

Data Table Address

Size in Bytes

Extended Routing…

Service

(1)

Instance

(2)

1

CIP Generic

N50:0

2

(3)

RIX16:0

Write Parameter

140 (Dec.)

Controller port to which the network is connected.

Used to access the Parameter Object in the adapter.

An unused controller data table address containing the message

instruction. This address is the starting word of the destination file.

Number of bytes to be transferred. Each byte size is an 8-bit integer.

An unused routing information file for the controller.

Code for the requested service.

Instance number is the same as the parameter number.

MultiHop Tab

Example Value

Description

To Address

10.91.100.79

IP address of the adapter connected to the drive.

(1)

The default setting for Service is ‘Custom’, enabling entry of a Service Code not available from the Service pull-down menu. When

choosing a Service other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically assigned to the Service

Code box which is dimmed (unavailable).

(2)

Only drive parameters (Port 0) can be written to using Parameter Object Class code 0x0F. To write to a parameter of a peripheral in

another port, use DPI Parameter Object Class code 0x93 (see

page 6-63

).

(3)

In this example, Accel Time 1 is a 16-bit integer parameter requiring the Size in Bytes field to be set to ‘2’. If the parameter being

written to is a 32-bit integer, the Size in Bytes must be set to ‘4’. When using a PowerFlex 700S or PowerFlex 750-Series drive, Accel

Time 1 is a floating point number requiring the Size in Bytes to be set to ‘4’. See the drive documentation to determine the size of the

parameter and its data type (16-bit or 32-bit integer or REAL).

Advertising