Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 199

Advertising
background image

Using Explicit Messaging

6-73

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

MicroLogix 1100/1400 Controller Example Scattered Write Request Data

In this message example, we use the data table addresses in

Figure 6.93

to

store the request values to be written to these drive parameters.

See

DPI Parameter Object on page C-16

(Class code 0x93) or

Host DPI

Parameter Object on page C-30

(Class code 0x9F) for parameter

numbering.

Figure 6.93

or

Figure 6.96

shows the parameter values.

Figure 6.93 Example Scattered Write Request Data File for PowerFlex 7-Class Drive

MicroLogix 1100/1400 Controller Example Scattered Write Response Data

In this message example, we use the data table addresses in

Figure 6.94

to

store the response values that were written to the requested drive
parameters. Values of ‘0’ indicate no errors occurred.

Figure 6.94 Example Scattered Write Response Data File for PowerFlex 7-Class Drive

The PowerFlex 750-Series drive uses 32-bit integer and REAL parameters.
A COP or CPW command must be used to copy the 16-bit integer or REAL
values to the N90 integer array.

Figure 6.95

shows the ladder logic used for

this example. If the parameter data type is a 32-bit integer, the data remains
split into two 16-bit integers since there are no 32-bit integers in the

PowerFlex 7-Class

Drive Parameter

Address Write Value

PowerFlex 750-Series

Drive Parameter

Write Value Data Type

141 - [Accel Time 2]

N90:1

11.1 Sec.

536 - [Accel Time 2]

11.1 Sec.

REAL

143 - [Decel Time 2]

N90:4

22.2 Sec.

538 - [Decel Time 2]

22.2 Sec.

REAL

105 - [Preset Speed 5]

N90:7

33.3 Hz.

725 - [Zero Position]

33

32-bit integer

106 - [Preset Speed 6]

N90:10

44.4 Hz.

21555 - [Port 5: Analog In0 Hi]

5.5

REAL

107 - [Preset Speed 7]

N90:13

55.5 Hz.

780 - [PTP Setpoint]

-75,555

32-bit integer