Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 162

Advertising
background image

6-36

Using Explicit Messaging

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

SLC 500 Controller Explicit Messaging Using the Generic Get/Set

Attribute Service

SLC 500 Controller Example Ladder Logic Program to Read a Single Parameter

A Generic Get Attribute Single message is used to read a single parameter.
This read message example reads the value of parameter 003 - [Output
Current] in a PowerFlex 7-Class drive.

Important: See

Table 6.A on page 6-2

for limitations of PowerFlex 7-Class

and PowerFlex 750-Series drives when using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class
code 0x9F for explicit messaging.

Figure 6.42 Example Ladder Logic to Read a Single Parameter