Figure 4.7 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 72

Advertising
background image

4-26

Configuring the I/O

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Figure 4.7 PLC-5 Message Configuration Screens for the Control Timeout

General Tab Box

Setting

This PLC-5
Communication Command

PLC-5 Typed Write. The controller type and command type for the controller to write the control

timeout value to the drive.

Data Table Address

(1)

N20:0. An unused controller data table address containing the control timeout value to be written.

Size in Elements

(2)

1. Number of elements (words) to be transferred. Each element size is a 16-bit integer.

Port Number

2. Controller port to which the network is connected.

Target Device (data for adapter/drive)
Data Table Address

(3)

N42:3. Specific starting address of the destination file in the drive.

MultiHop

Yes. Enables communication to allow network messaging to be routed to the adapter/drive. When

‘Yes’ is selected, a MultiHop tab appears on the message configuration screen.

MultiHop Tab Box

Setting

To Address

10.91.100.79. The IP address of the adapter connected to the drive.

(1)

For details on data table addresses for this example project, see

Table 5.G

Table 5.J

starting on

page 5-23

.

(2)

For details to determine element size for a specific drive, see

Understanding Controller Data Table Addresses on page 5-22

.

(3)

For details on setting the control timeout value and its function, see

N-Files on page C-10

. The Control Timeout (N42:3) is stored in RAM. If the

20-COMM-E adapter is power cycled, the Control Timeout Message must be re-sent. If the Control Timeout is not changed from a non-zero

value, the control message (

page 4-29

) will error out.

TIP: The Control Timeout (N42:3) must be changed to a non-zero value
(5…20 seconds recommended). If the Control Timeout is not changed from
a non-zero value, the control message (

page 4-29

) will error out. The

Control Timeout is stored in RAM. If the adapter is power cycled, the
Control Timeout Message must be re-sent.