Viewing and clearing events, Viewing and clearing events -6 – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 206

Advertising
background image

7-6

Troubleshooting

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Viewing and Clearing

Events

The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry is put into the
event queue. You can view the event queue with any of these drive
configuration tools:

• LCD PowerFlex 7-Class HIM

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 1.01 or later

The event queue can contain up to 32 entries. Eventually the event queue
will become full, since its contents are retained after adapter resets. At that
point, a new entry replaces the oldest entry. Only an event queue clear
operation or adapter power cycle will clear the event queue contents.

Resetting the adapter to defaults has no effect on the event queue.

45

46

47

48

Gateway Act 1

Gateway Act 2

Gateway Act 3

Gateway Act 4

Value of each byte in the adapter’s present gateway address. A

value of ‘0’ appears if the adapter does not currently have a gateway

address.

49

EN Rx Overruns

Number of receive buffer overruns reported by the Ethernet

hardware.

50

EN Rx Packets

Number of Ethernet packets that the adapter has received.

51

EN Rx Errors

Number of receive errors reported by the Ethernet hardware.

52

EN Tx Packets

Number of Ethernet packets that the adapter has sent.

53

EN Tx Errors

Number of transmit errors reported by the Ethernet hardware.

54

Last TCP Reset

Last reason that the adapter reset or rejected a TCP/IP connection.

55

Missed IO Pkts

Number of incoming I/O connection packets that the adapter did not

receive.

56

OPT Status

The operating status of optional I/O board in DPI External Comms

Kit. For the meanings of the individual bits, see

Viewing Optional I/O

Diagnostic Items on page 9-4

.

57

OPT RX Errors

Number of optional I/O board receive errors.

58

OPT FW Version

Firmware version of optional I/O board (in DPI External Comms Kit).

Table 7.A Adapter Diagnostic Items (Continued)

No. Name

Description

255.255.255.255

[Gateway Act 1]

[Gateway Act 2]

[Gateway Act 3]

[Gateway Act 4]

Advertising