Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 208

Advertising
background image

7-8

Troubleshooting

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

11

Dup Port Flt

Another peripheral with the same port number is already in use.

12

Type 0 Login

The adapter has logged in for Type 0 control.

13

Type 0 Time Flt

The adapter has not received a Type 0 status message within the specified time.

14

DL Login

The adapter has logged into a Datalink.

15

DL Reject Flt

The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another

peripheral.

16

DL Time Flt

The adapter has not received a Datalink message within the specified time.

17

Reserved

Not used.

18

Control Disabled

The adapter has sent a ‘Soft Control Disable’ command to the drive.

19

Control Enabled

The adapter has sent a ‘Soft Control Enable’ command to the drive.

20

Message Timeout

A Client-Server message sent by the adapter was not completed within 1 sec.

21

Flt Cfg Error

One of the Flt Cfg xx parameters is set to a value greater than 65535 and the drive requires a 16-bit value.

22

App Updated

Startup sequence detected new application firmware.

23

EN Comm Flt

The adapter detected a communications fault on the network.

24

EN Sent Reset

The adapter received a reset from the network.

25

EN Close Flt

An I/O connection from the network to the adapter was closed.

26

EN Idle Flt

The adapter is receiving ‘idle’ packets from the network.

27

EN Open

An I/O connection from the network to the adapter has been opened.

28

EN Timeout Flt

An I/O connection from the network to the adapter has timed out.

29

PCCC IO Close

The device sending PCCC Control messages to the adapter has set the PCCC Control Timeout to zero.

30

PCCC IO Open

The adapter has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a

non-zero value).

31

PCCC IO Time Flt

The adapter has not received a PCCC Control message for longer than the PCCC Control Timeout.

32

Watchdog T/O Flt

The software detects a failure.

33

EEPROM Init

Startup sequence detected a blank EEPROM map revision.

34

Normal Startup

The adapter successfully started up.

35

Manual Reset

The adapter was reset by changing its Reset Module parameter.

36

EN Link Down

The Ethernet link was removed from the adapter.

37

EN Link Up

An Ethernet link is available for the adapter.

38

BOOTP Response

The adapter received a response to its BOOTP request.

39

Dup IP Addr

The adapter uses the same IP address as another device on the network.

40

Peer IO Open

The adapter received the first Peer I/O message.

41

Peer IO Time Flt

The adapter has not received a Peer I/O message for longer than the Peer I/O Timeout.

42

Email Failed

The adapter encountered an error attempting to send a requested e-mail message.

43

Msg Ctrl Open

The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing

control messages to be sent to the adapter.

44

Msg Ctrl Close

The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing

control messages to be sent to the adapter.

45

Msg Ctrl Timeout

The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.

46

OPT Open

The adapter began exchanging I/O data with the I/O option of the DPI External Comms Kit.

47

OPT Close

The adapter forced a fault condition on the I/O option of the DPI External Comms Kit.

48

OPT Timeout

Communication between the adapter and I/O option of the DPI External Comms Kit was disrupted.

Table 7.B Adapter Events (Continued)

Code

Event

Description