Configuring the Adapter

3-9

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.

3. Set the bits in Parameter 36 - [M-S Output].

This parameter determines the data transmitted from the drive to the
scanner. A ‘1’ enables the I/O and a ‘0’ disables the I/O.

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.

4. Reset the adapter (see

Resetting the Adapter on page 3-16

).

The adapter is ready to receive I/O from the master (that is, scanner). You
must now configure the scanner to recognize and transmit I/O to the adapter.
See

Chapter 4

,

Configuring the I/O

.

Setting the Adapter to Transmit Peer-to-Peer Data (Drive-to-Drive

Communication)

1. Verify that Parameter 51 - [Peer Out Enable] is set to ‘0’ (Off).

This parameter must be Off while you configure peer output
parameters.

2. Set Parameter 49 - [Peer A Output] to select the source of the data to

output to the network.

Bit

Description

0

Status/Feedback (Default)

1

Datalink A Output

2

Datalink B Output

3

Datalink C Output

4

Datalink D Output

5…15

Not Used

Port 5 Device
20-COMM-E
Parameter #: 36

M-S Output

x x x x x x x x x x x 0 0 0 0

1

Status/Fdbk

b00

Value Setting
0

Off (Default)

1

On

Port 5 Device
20-COMM-E
Parameter #: 51

Peer Out Enable

0

Off

Port 5 Device
20-COMM-E
Parameter #: 49

Peer A Output

1

Cmd/Ref

Value

Description

0

Off (Default)

1

Logic Command/Reference

2…5

Datalink A, B, C, or D Input

6…9

Datalink A, B, C, or D Output