Table 4.A Drives with 16-bit Reference/Feedback and 16-bit Datalinks

These products include the following:

Table 4.B Drives with 16-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

Table 4.C Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

• PowerFlex 70 drives with standard or enhanced control

• SMC Flex smart motor controllers

• PowerFlex 700 drives with standard control

• SMC-50 smart motor controllers

• PowerFlex 700H drives

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (16-bit) User Configured Settings

A

B

C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

4

2

…0 0001

…0 0001

…0 0001

6

4

…0 0011

…0 0011

…0 0011

8

6

…0 0111

…0 0111

…0 0111

10

8

…0 1111

…0 1111

…0 1111

12

10

…1 1111

…1 1111

…1 1111

• PowerFlex 700 drives with vector control

• PowerFlex Digital DC drives

• PowerFlex 700L drives with 700 control

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (32-bit) User Configured Settings

A

B

C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

4

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Logic

Command/

Status

Ref/Fdbk

(32-bit)

Datalinks (32-bit) User Configured Settings

A

B

C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

6

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

TIP: For instructions on configuring the I/O for the adapter using
Parameter 23 - [DPI I/O Cfg] and its Master-Slave Hierarchy using
Parameters 35 - [M-S Input] and 36 - [M-S Output], see

Setting the I/O Configuration on page 3-7

.