Logic Status Word

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status

Description

x

Ready

0 = Not Ready (Par. 1403)

1 = Ready

x

Active

0 = Not Active (Running)

1 = Active

x

Command

Direction

0 = Reverse

1 = Forward

x

Actual Direction

0 = Reverse

1 = Forward

x

Accel

0 = Not Accelerating

1 = Accelerating

x

Decel

0 = Not Decelerating

1 = Decelerating

x

Alarm

0 = No Alarm (Par. 1380)

1 = Alarm

x

Fault

0 = No Fault (Par. 1351)

1 = Fault

x

At Speed

0 = Not At Reference

1 = At Reference

x

x

x

Local Control

(1)

000 = Port 0 (TB)

001 = Port 1

010 = Port 2

011 = Port 3

100 = Port 4

101 = Port 5

110 = Reserved

111 = No Local

x

x

x

x

Reference Source 0000 = Spd Ref A Auto (Par. 44)

0001 = Spd Ref B Auto (Par. 48)

0010 = Preset Spd 2 Auto

0011 = Preset Spd 3 Auto

0100 = Preset Spd 4 Auto

0101 = Preset Spd 5 Auto

0110 = Preset Spd 6 Auto

0111 = Preset Spd 7 Auto

1000 = Term Blk Manual

1001 = DPI 1 Manual

1010 = DPI 2 Manual

1011 = DPI 3 Manual

1100 = DPI 4 Manual

1101 = DPI 5 Manual

1110 = Reserved

1111 = Jog Ref

(1)

See ‘Owners’ in drive User Manual for further information.