Table 5.c – Rockwell Automation 20-COMM-E PowerFlex EtherNet/IP Adapter User Manual

Page 96

Advertising
background image

5-4

Using the I/O

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

Table 5.C ControlLogix Controller I/O Image for Drives with 32-bit Reference/

Feedback and 32-bit Datalinks – Using Generic Profile

These products include the following:

PLC-5, SLC 500, or MicroLogix 1100/1400 Controller Image

The I/O image for these controllers always has 19 words of output and 19
words of input. However, depending on the size of the drive’s Reference/
Feedback and Datalinks, and the number of Datalinks used, specific words
in the I/O image may not be used.

Table 5.D

,

Table 5.E

, and

Table 5.F

show

the I/O image when using various PowerFlex drives, and all Datalinks
enabled.

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Word

Output I/O

Word

Input I/O

0

Logic Command

0

Pad Word

1

Not Used

1

Pad Word

2

Reference (LSW)

2

Logic Status

3

Reference (MSW)

3

Not Used

4

Datalink In A1 (LSW)

4

Feedback (LSW)

5

Datalink In A1 (MSW)

5

Feedback (MSW)

6

Datalink In A2 (LSW)

6

Datalink Out A1 (LSW)

7

Datalink In A2 (MSW)

7

Datalink Out A1 (MSW)

8

Datalink In B1 (LSW)

8

Datalink Out A2 (LSW)

9

Datalink In B1 (MSW)

9

Datalink Out A2 (MSW)

10

Datalink In B2 (LSW)

10

Datalink Out B1 (LSW)

11

Datalink In B2 (MSW)

11

Datalink Out B1 (MSW)

12

Datalink In C1 (LSW)

12

Datalink Out B2 (LSW)

13

Datalink In C1 (MSW)

13

Datalink Out B2 (MSW)

14

Datalink In C2 (LSW)

14

Datalink Out C1 (LSW)

15

Datalink In C2 (MSW)

15

Datalink Out C1 (MSW)

16

Datalink In D1 (LSW)

16

Datalink Out C2 (LSW)

17

Datalink In D1 (MSW)

17

Datalink Out C2 (MSW)

18

Datalink In D2 (LSW)

18

Datalink Out D1 (LSW)

19

Datalink In D2 (MSW)

19

Datalink Out D1 (MSW)

20

Datalink Out D2 (LSW)

21

Datalink Out D2 (MSW)

Advertising