Configuring the I/O

4-21

20-COMM-E EtherNet/IP Adapter User Manual

Publication 20COMM-UM010G-EN-P

2. Click Download to download the configuration to the controller.

When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O OK box in the upper-left of the
screen should be steady green.

3. Select File > Save.

If this is the first time you saved the project, the Save As dialog box
appears.

a. Navigate to a folder.

b. Type a file name.

c.

Click Save to save the configuration as a file on your computer.

To be sure that the present project configuration values are saved,
RSLogix 5000 software prompts you to upload them. Click Yes to
upload and save the values.

4. Configure any Datalinks in the drive (for example, Datalink parameters

300…317 in PowerFlex 70/700 drives) that were enabled in the
controller and adapter during I/O configuration (

Table 4.A

,

Table 4.B

,

or

Table 4.C

).

Each Datalink being used must be assigned to a specific parameter in
the drive or connected peripheral. If this is not done, the controller will
receive or send placeholder data instead of actual drive or peripheral
parameter values.

5. Place the controller in Remote Run or Run Mode.