Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 112

Advertising
background image

112

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Chapter 7

Troubleshooting

Table 12 - Adapter Events

Code

Event

Description

Adapter Events

1

No Event

Text displayed in an empty event queue entry.

2

Device Power Up

Power was applied to the adapter.

3

Device Reset

The adapter was reset.

4

EEPROM CRC Error

The EEPROM checksum/CRC is incorrect, which limits adapter functionality. Default
parameter values must be loaded to clear this condition.

5

App Updated

The adapter application firmware was flash updated.

6

Boot Updated

The adapter boot firmware was flash updated.

7-24

Reserved

DPI Events

25

DPI Manual Reset

The adapter was reset.

26-28

Reserved

Network Events

29

Net Link Up

An network link was available for the adapter.

30

Net Link Down

The network link was removed from the adapter.

31

Net Dup Address

The adapter uses the same IP address as another device on the network.

32

Net Comm Fault

The adapter detected a communications fault on the network.

33

Net Sent Reset

The adapter received a reset from the network.

34

Net IO Close

An I/O connection from the network to the adapter was closed.

35

Net Idle Fault

The adapter received ‘idle’ packets from the network.

36

Net IO Open

An I/O connection from the network to the adapter has been opened.

37

Net IO Timeout

An I/O connection from the network to the adapter has timed out.

38

Net IO Size Err

The adapter received an incorrectly sized I/O packet.

39

PCCC IO Close

The device sending PCCC Control messages to the adapter has set the PCCC Control
Timeout to zero.

40

PCCC IO Open

The adapter has begun receiving PCCC Control messages (the PCCC Control Timeout
was previously set to a non-zero value).

41

PCCC IO Timeout

The adapter has not received a PCCC Control message for longer than the PCCC Control
Timeout.

42

Msg Ctrl Open

The timeout attribute in either the CIP Register or Assembly object was written with a
non-zero value, allowing control messages to be sent to the adapter.

43

Msg Ctrl Close

The timeout attribute in either the CIP Register or Assembly object was written with a
zero value, disallowing control messages to be sent to the adapter.

44

Msg Ctrl Timeout

The timeout attribute in either the CIP Register or Assembly object elapsed between
accesses of those objects.

45

Peer IO Open

The adapter received the first Peer I/O message.

46

Peer IO Timeout

The adapter has not received a Peer I/O message for longer than the Peer I/O Timeout.

47-54

Reserved

55

BOOTP Response

The adapter received a response to its BOOTP request.

56

E-mail Failed

The adapter encountered an error attempting to send a requested e-mail message.

57

Option Card Flt

The adapter experienced a generic fault condition (drive only).

58

Module Defaulted

The adapter has been set to defaults.