Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 27

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
27
Configuring the Adapter
Chapter 3
1.
Verify that Parameter 36 - [BOOTP] is set to ‘1’ (Enabled).
2.
Note the adapter’s hardware Ethernet Address (MAC), which will be used
in step 7.
There are two ways to do this:
•
Remove the PowerFlex 755 drive cover and locate the adapter’s
hardware Ethernet Address (MAC) label on the drive’s Main Control
Board (
Figure 4
).
Figure 4 - Adapter Hardware Address Label Location
•
Use the HIM to scroll to drive Port 13 and access the embedded
EtherNet/IP adapter DIAGNOSTIC folder screen. Then scroll to
Diagnostic Items 43…48 (HW Addr 1…6) to view the adapter’s
hardware Ethernet Address (MAC). Finally, convert these decimal
values to a hex value.
3.
On a computer connected to the EtherNet/IP network, start the
BOOTP/DHCP software.
The BOOTP/DHCP Server dialog box appears.
Value
Setting
0
Disabled
1
Enabled (Default)
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit BOOTP
Enabled
1
0 << 1
0
9
8
2
1
Ethernet Address
(MAC) label location
Drive Control Pod
Ethernet
Connector