Configuring the Adapter

Chapter 3

1.

Verify that Parameter 36 - [BOOTP] is set to ‘1’ (Enabled).

2.

Note the adapter’s hardware Ethernet Address (MAC), which will be used
in step 7.

There are two ways to do this:

Remove the PowerFlex 755 drive cover and locate the adapter’s
hardware Ethernet Address (MAC) label on the drive’s Main Control
Board (

Figure 4

).

Figure 4 - Adapter Hardware Address Label Location

Use the HIM to scroll to drive Port 13 and access the embedded
EtherNet/IP adapter DIAGNOSTIC folder screen. Then scroll to
Diagnostic Items 43…48 (HW Addr 1…6) to view the adapter’s
hardware Ethernet Address (MAC). Finally, convert these decimal
values to a hex value.