Configuring the I/O

If a configuration signature for the drive/peripheral indicates a
configuration download needs to be performed for the given port.

Whether Firmware Supervisor is enabled and needs to upgrade the drive
and/or any peripherals prior to ADC taking place. Note that updating
drives or peripherals will add significantly to the connection process time
and will be similar to the time it takes to manually update using
ControlFLASH software.

If a 20-750-S1 Safe Speed Monitor option module, which requires a
manual ‘step’ in its configuration process, is used.

If a DeviceLogix program (Port 14) is used.

See the PowerFlex 750-Series AC Drive Programming Manual, publication

750-

PM001

, for information about the drive status indicators. An operational drive in

a running Logix system will have the following status indicator states.

Additional information may also be displayed on the HIM if it is present
(upgrade status, and so forth).

If ADC is unsuccessful, the ENET status indicator will be flashing green or off,
and RSLogix 5000 software can be used to get additional information. When
online, the drive at issue should have a yellow triangle

next to it in the

RSLogix 5000 project's I/O Configuration folder. Double-click the drive to
open the Drive AOP. The Connection tab will show a Module Fault code and
the Drive tab will identify issues to the Port level.

IMPORTANT

ADC can automatically reset the drive as part of the configuration process. This
is done because some parameters require a reset before they take effect. If a
drive is being replaced with an out-of-the-box drive, you will typically see at
least two resets during the ADC process—one for the parameters in the drive
(Port 0) and, for a PowerFlex 755 drive, one for the parameters in the
embedded EtherNet/IP adapter (Port 13).

Status
Indicator

Color

State

Description

STS

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

ENET

Green

Steady

Embedded ENET adapter is properly connected and communicating on the network.

LINK

Green

Flashing

Embedded ENET adapter is properly connected and transmitting data packets on the
network.

ADC Status Field

Description

Running

Any desired configuration is complete, and the I/O connection is running.

Configuring

ADC is currently updating the configuration of the drive or one of its peripherals. Clicking the
Connection tab will show which device is being updated.

Firmware Updating

ADC is currently updating the firmware of the drive or one of its peripherals. Clicking the Drive
tab will show which device is being updated.