Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual
Page 29

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013
29
Configuring the Adapter
Chapter 3
7.
In the BOOTP/DHCP Request History list, either double-click the
adapter’s Ethernet Address (MAC) noted in step 2, or click New in the
Relation List.
The New Entry dialog box appears. In the first instance, the Ethernet
Address (MAC) is automatically entered. In the latter instance, it must be
manually entered.
8.
Edit the following:
9.
Click OK to apply the settings.
The adapter appears in the Relation List with the new settings.
10.
To permanently assign this configuration to the adapter, select the device
in the Relation List and click Disable BOOTP/DHCP.
When power is cycled on the adapter, it will use the configuration you
assigned it and not issue new BOOTP requests.
11.
From the File menu, choose Save to save the Relation List.
Box
Type
IP Address
(1)
(1) For definition of this term, see the
A unique IP address for the adapter
Host Name
Optional
Description
Optional
TIP
To enable BOOTP for an embedded adapter that has had BOOTP
disabled, first select the adapter in the Relation List. Then click Enable
BOOTP and, lastly, reset the adapter or power cycle the drive.