Quick start – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 16

Advertising
background image

16

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Chapter 1

Getting Started

Quick Start

This section is provided to help experienced users quickly start using the
embedded EtherNet/IP adapter. If you are unsure how to complete a step, refer to
the referenced chapter.

Step

Action

See

1

Review the safety precautions for the adapter.

Throughout this manual

2

Verify that the PowerFlex drive is properly installed.

PowerFlex 750-Series AC Drive
Installation Instructions,
publication

750-IN001

3

Set the adapter IP address.

a. When using the adapter switches, set the IP address now and

proceed with step 4.

When using a BOOTP server, or adapter parameters instead to set the
IP address, first perform step 3b and 3c, and all of step 4. Then
proceed with step 5.

b. Verify that the PowerFlex drive is not powered.

c. Connect the embedded EtherNet/IP adapter to the network with an

Ethernet cable.

Chapter 2

,

Installing the Adapter

4

Apply power to the drive.

a. Replace the drive cover or close the drive door.

b. Apply power to the drive.

The embedded EtherNet/IP adapter receives power from the drive.
The status indicators should be green. If they flash red, there is a
problem. See

Chapter 7

, Troubleshooting.

c. Configure and verify key drive parameters.

Chapter 2

,

Installing the Adapter

5

Configure the adapter for your application.

Set embedded EtherNet/IP adapter parameters for the following functions
as required by your application:

IP address, subnet mask, and gateway address (only when not using

adapter switches)

Data rate
I/O configuration
Master-Slave or Peer-to-Peer hierarchy
Fault actions
Web enable and features

Chapter 3

,

Configuring the Adapter

6

Configure the controller to communicate with the adapter.

Use a controller configuration tool, such as RSLogix software, to configure
the master on the network to recognize the embedded EtherNet/IP adapter
and drive.

Chapter 4

,

Configuring the I/O

7

Create a ladder logic program.

Use a controller configuration tool, such as RSLogix software, to create a
ladder logic program that enables you to do the following:

Control the drive, via the embedded EtherNet/IP adapter, by using I/O.
Monitor or configure the drive by using explicit messages.

Chapter 5

,

Using the I/O

Chapter 6

,

Using Explicit Messaging

Advertising