Configuring and verifying key drive parameters – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 22

Advertising
background image

22

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Chapter 2

Installing the Adapter

Table 1 - Drive and Adapter Start-Up Status Indications

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see

page 108

.

Configuring and Verifying Key Drive Parameters

The PowerFlex 755 drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.

The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.

1.

Verify that drive Parameter 301 - [Access Level] is set to ‘1’ (Advanced) or
‘2’ (Expert) to access the required parameters in this procedure.

Item

Name

Color

State

Description

Drive STS Indicator

STS
(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable) alarm condition exists – drive continues to run. When stopped,
a start inhibit condition exists and the drive cannot be started (see drive parameter 933 - [Start Inhibit]).

Steady

A type 1 (user configurable) alarm condition exists, but the drive continues to run.

Red

Flashing

A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is cleared.

Steady

A non-resettable fault has occurred.

Red/Yellow

Flashing Alternately

A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not enabled, acts like
a major fault. When running, the drive continues to run. System is brought to a stop under system control.
The fault must be cleared to continue.

Yellow/Green

Flashing Alternately

When running, a type 1 alarm exists.

Green/Red

Flashing Alternately

Drive is firmware updating.

Embedded EtherNet/IP Adapter Status Indicators

ENET

Unlit

Off

Adapter and/or network is not powered, adapter is not properly connected to the network, or adapter
needs an IP address.

Red

Flashing

An EtherNet/IP connection has timed out.

Steady

Adapter failed the duplicate IP address detection test.

Red/Green

Flashing Alternately

Adapter is performing a self-test.

Green

Flashing

Adapter is properly connected, but is not communicating with any devices on the network.

Steady

Adapter is properly connected and communicating on the network.

LINK

Unlit

Off

Adapter is not powered or is not transmitting on the network.

Green

Flashing

Adapter is properly connected and transmitting data packets on the network.

Steady

Adapter is properly connected, but is not transmitting on the network.