Parameter list – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Appendix B

Adapter Parameters

Parameter List

Parameter

No.

Name and Description

Details

01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16

[DL From Net 01]
[DL From Net 02]
[DL From Net 03]
[DL From Net 04]
[DL From Net 05]
[DL From Net 06]
[DL From Net 07]
[DL From Net 08]
[DL From Net 09]
[DL From Net 10]
[DL From Net 11]
[DL From Net 12]
[DL From Net 13]
[DL From Net 14]
[DL From Net 15]
[DL From Net 16]
Sets the port number and parameter number to which the
selected Datalinks should connect. Each selected port/parameter
will be written with data received from the network. These are
parameters written by the controller (outputs from the
controller).

If setting the value manually, the parameter value = (10000 *
port number) + (destination parameter number). For example,
suppose you want to use Parameter 01 - [DL From Net 01] to
write to Parameter 01 of an optional encoder card plugged into
drive Port 5. The value for Parameter 01 - [DL From Net 01]
would be 50001 [(10000 * 5) + 1].

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

159999

Type:

Read/Write

Reset Required:

No

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

[DL To Net 01]
[DL To Net 02]
[DL To Net 03]
[DL To Net 04]
[DL To Net 05]
[DL To Net 06]
[DL To Net 07]
[DL To Net 08]
[DL To Net 09]
[DL To Net 10]
[DL To Net 11]
[DL To Net 12]
[DL To Net 13]
[DL To Net 14]
[DL To Net 15]
[DL To Net 16]
Sets the port number and parameter number to which the
selected Datalinks should connect. Each selected port/parameter
will be read and their values transmitted over the network to the
controller. These are parameters read by the controller (inputs to
the controller).

If setting the value manually, the parameter value = (10000 *
port number) + (origination parameter number). For example,
suppose you want to use Parameter 17 - [DL To Net 01] to
read Parameter 02 of an optional I/O card plugged into drive Port
6. The value for Parameter 17 - [DL To Net 01] would be 60002
[(10000 * 6) + 2].

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

159999

Type:

Read/Write

Reset Required:

No

33

[Port Number]
Displays the drive port to which the embedded EtherNet/IP
adapter is dedicated. This is always Port 13.

Value:

13

Type:

Read Only

34

[DLs From Net Act]
Displays the number of controller-to-drive Datalinks that the
drive is using based on the I/O connection opened by the
controller.

Minimum:

0

Maximum:

16

Type:

Read Only

Advertising