Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 61

Advertising
background image

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

61

Configuring the I/O

Chapter 4

When converting RSLogix 5000 projects, version 16.00…19.00, to version
20.00 projects (with version 4.01 Drive AOPs), ADC will be enabled by
default for any drive that supports ADC, such as PowerFlex 753 drives
with firmware 7.001 or later using a 20-750-ENETR EtherNet/IP option
module, or PowerFlex 755 drives with firmware 4.001 or later.

RSLogix 5000 software, version 20.00 can be updated with version 4.02 (or later)
Drive AOPs, which are available via free download at:

http://www.ab.com/support/abdrives/webupdate/software.html

Version 4.02 (or later) Drive Add-on Profiles (AOPs)

Version 4.02

Drive AOPs require user action to enable ADC. This helps verify

that the user understands ADC operation prior to turning it on. Note the
following ADC operating status when using version 4.02 (or later) Drive AOPs:

When adding a new drive, ADC is disabled by default for any drive that
supports ADC, such as PowerFlex 753 drives with firmware 7.001 or later
using a 20-750-ENETR EtherNet/IP option, or PowerFlex 755 drives
with firmware 4.001 or later.

When converting an earlier RSLogix 5000 project to a version 20.00
project that has been updated with version 4.02 (or later) Drive AOPs or
when updating a project created with version 4.01 Drive AOPs, any ADC
settings will be passed through as-is for drives that support ADC. For
example:

If ADC was disabled for a drive in a previous project, it will remain
disabled.

If ADC was enabled for a drive using version 4.01 Drive AOPs and that
project was later updated to version 4.02 (or later) Drive AOPs, it will
remain enabled.

Version 4.02 (or later) Drive AOPs also have an ADC icon on the Drive tab to
show general ADC enable/disable status for the drive:

Clicking on the ADC icon will launch the ADC configuration dialog box. This
provides a single, convenient location to enable/disable ADC for any of the ports
on the drive.

TIP

To identify the Drive AOP version, click the icon in the upper-left corner of the
Module Properties dialog box and select ‘About Module Profile’.

Icon

Meaning

No ports on the drive have ADC enabled.

At least one port on the drive has ADC enabled.

ADC is not supported.