Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 131

Advertising
background image

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

131

Adapter Parameters

Appendix B

54

[Comm Flt Action]
Sets the action that the adapter and drive will take if the adapter
detects that I/O communication has been disrupted. This setting
is effective only if I/O that controls the drive is transmitted
through the adapter. When communication is re-established, the
drive will automatically receive commands over the network
again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

55

[Idle Flt Action]
Sets the action that the adapter and drive will take if the adapter
detects that the controller is in program mode or faulted. This
setting is effective only if I/O that controls the drive is
transmitted through the adapter. When the controller is put back
in Run mode, the drive will automatically receive commands over
the network again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required:

No

Parameter

No.

Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. Parameter 54
- [Comm Flt Action]
lets you determine the action of the adapter and
connected drive if I/O communication is disrupted. By default, this
parameter faults the drive. You may configure this parameter so that the
drive continues to run, however, precautions should be taken to verify
that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a
disconnected cable).

ATTENTION: Risk of injury or equipment damage exists. Parameter 55
- [Idle Flt Action]
lets you determine the action of the adapter and
connected drive when the controller is idle. By default, this parameter
faults the drive. You may configure this parameter so that the drive
continues to run, however, precautions should be taken to verify that
the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a controller
in idle state).