Appendix a, Specifications, Communications – Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 125: Regulatory compliance, Communications regulatory compliance

Advertising
background image

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

125

Appendix

A

Specifications

This appendix presents the specifications for the adapter.

Communications

Regulatory Compliance

NOTE:

This is a product of category C2 according to IEC 61800-3. In a

domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.

Network

Protocol
Data Rates

EtherNet/IP
10 Mbps Full Duplex, 10 Mbps Half Duplex, 100 Mbps Full Duplex, or 100 Mbps
Half Duplex

Connection Limits

30 TCP connections
16 simultaneous CIP connections including 1 exclusive-owner I/O connection

The following activities use a CIP connection:
Class I I/O connections (for example, from a ControlLogix controller) or

‘Integrated Motion on the EtherNet/IP network’ connection

Explicit messaging where ‘connected’ is chosen (for example, in a check box

in RSLogix 5000 software)

DriveExecutive connections to the drive

The following activities do not use a CIP connection:
Explicit messaging-based control using PCCC or the Register or Assembly

objects

Explicit messaging where ‘connected’ is not chosen, which is typically the

default

DriveExplorer software connections to the drive

Requested Packet Interval (RPI)

2 ms minimum

‘Integrated Motion on the
EtherNet/IP network’ Coarse
Update Rate

2 ms minimum

Packet Rate

Up to 400 total I/O packets per second (200 in and 200 out)

Drive

Protocol
Data Rate

DPI
500 Kbps

UL

UL508C

cUL

CAN / CSA C22.2 No. 14-M91

CE

EN50178 and EN61800-3

CTick

EN61800-3

Advertising