Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 54

Advertising
background image

54

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Chapter 4

Configuring the I/O

8.

Click the Connection tab.

9.

In the ‘Requested Packet Interval (RPI)’ box, set the value to 2.0
milliseconds or greater (default is 20.0 milliseconds).

This value determines the maximum interval that a controller should use
to move data to and from the adapter. To conserve bandwidth, use higher
values for communicating with low priority devices.

The ‘Inhibit Module’ box, when checked, inhibits the module from
communicating with the RSLogix 5000 project. When the ‘Major Fault
On’ box is checked, a major controller fault will occur when the module’s
connection fails while the controller is in the Run Mode. For this example,
leave the ‘Inhibit Module’ and ‘Major Fault On’ boxes unchecked.

Unicast support has been added to RSLogix 5000 software, version 18.00
or later. Unicast is recommended whenever possible. For the benefits of
unicast operation, see

Preparing for an Installation on page 17

.

10.

Click the Port Configuration tab.

11.

In the Port Configuration tab dialog box, edit the following information.

Box

Setting

IP Address

The IP address of the adapter that was already set in the General tab. This field is not
configurable (grayed out).

Subnet Mask

The Subnet Mask configuration setting of the network. This setting must match the
setting of other devices on the network (for example, 255.255.255.0).

Gateway Address

The Gateway Address configuration setting of the network. This setting must match the
setting of other devices on the network (for example, 10.91.100.1).