Rockwell Automation 20G PowerFlex 755 Drive Embedded EtherNet/IP Adapter User Manual

Page 86

Advertising
background image

86

Rockwell Automation Publication 750COM-UM001E-EN-P - October 2013

Chapter 5

Using the I/O

Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All
Versions

Adapter Parameter Settings for ControlLogix Controller Example

These adapter settings were used for the example ladder logic program in this
section.

Adapter Parameter

Value

Description

01 - [DL From Net 01]

370

Points to drive Par. 370 - [Stop Mode A]

02 - [DL From Net 02]

371

Points to drive Par. 371 - [Stop Mode B]

03 - [DL From Net 03]

535

Points to drive Par. 535 - [Accel Time 1]

04 - [DL From Net 04]

536

Points to drive Par. 536 - [Accel Time 2]

05 - [DL From Net 05]

537

Points to drive Par. 537 - [Decel Time 1]

06 - [DL From Net 06]

538

Points to drive Par. 538 - [Decel Time 2]

07 - [DL From Net 07]

539

Points to drive Par. 539 - [Jog Acc Dec Time]

08 - [DL From Net 08]

556

Points to drive Par. 556 - [Jog Speed 1]

09 - [DL From Net 09]

557

Points to drive Par. 557 - [Jog Speed 2]

10 - [DL From Net 10]

571

Points to drive Par. 571 - [Preset Speed 1]

11 - [DL From Net 11]

572

Points to drive Par. 572 - [Preset Speed 2]

12 - [DL From Net 12]

573

Points to drive Par. 573 - [Preset Speed 3]

13 - [DL From Net 13]

574

Points to drive Par. 574 - [Preset Speed 4]

14 - [DL From Net 14]

575

Points to drive Par. 575 - [Preset Speed 5]

15 - [DL From Net 15]

576

Points to drive Par. 576 - [Preset Speed 6]

16 - [DL From Net 16]

577

Points to drive Par. 577 - [Preset Speed 7]

17 - [DL To Net 01]

370

Points to drive Par. 370 - [Stop Mode A]

18 - [DL To Net 02]

371

Points to drive Par. 371 - [Stop Mode B]

19 - [DL To Net 03]

535

Points to drive Par. 535 - [Accel Time 1]

20 - [DL To Net 04]

536

Points to drive Par. 536 - [Accel Time 2]

21 - [DL To Net 05]

537

Points to drive Par. 537 - [Decel Time 1]

22 - [DL To Net 06]

538

Points to drive Par. 538 - [Decel Time 2]

23 - [DL To Net 07]

539

Points to drive Par. 539 - [Jog Acc Dec Time]

24 - [DL To Net 08]

556

Points to drive Par. 556 - [Jog Speed 1]

25 - [DL To Net 09]

557

Points to drive Par. 557 - [Jog Speed 2]

26 - [DL To Net 10]

571

Points to drive Par. 571 - [Preset Speed 1]

27 - [DL To Net 11]

572

Points to drive Par. 572 - [Preset Speed 2]

28 - [DL To Net 12]

573

Points to drive Par. 573 - [Preset Speed 3]

29 - [DL To Net 13]

574

Points to drive Par. 574 - [Preset Speed 4]

30 - [DL To Net 14]

575

Points to drive Par. 575 - [Preset Speed 5]

31 - [DL To Net 15]

576

Points to drive Par. 576 - [Preset Speed 6]

32 - [DL To Net 16]

577

Points to drive Par. 577 - [Preset Speed 7]

TIP

The [DL From Net xx] parameters are inputs into the drive that come from
controller outputs (for example, data to write to a drive parameter). The [DL To
Net xx]
parameters are outputs from the drive that go to controller inputs (for
example, data to read a drive parameter).