Configuring the I/O

Chapter 4

11.

RSLogix 5000 software will go to the Offline state, and the following
dialog box will appear.

Wait a short period of time for the store operation to complete, and then
attempt to go online with the controller again.

Special Considerations When Using a DeviceLogix Program

There are special considerations when a PowerFlex 750-Series drive has ADC
enabled and is running a DeviceLogix program. ADC will download the
DeviceLogix program after the drive is replaced but, by default, the program will
be disabled (not running) since the factory default setting is ‘Logic disabled’ for a
new replacement drive.

If you want the DeviceLogix program to be enabled (run) after ADC, you have to
configure the drive in your project to do this by performing the following steps.

1.

Select the PowerFlex 750-Series drive and click the Drive tab.

2.

Select the DeviceLogix Port in the device tree.

3.

Click the DeviceLogix icon to open the DeviceLogix Editor.

4.

From the Edit menu, choose Recovery Mode.

5.

Click Enabled to enable DeviceLogix after ADC.

If you do not set up the automatic method described above to enable
DeviceLogix after ADC, you can still do so manually. To enable the DeviceLogix
program, set DeviceLogix Parameter 53 - [DLX Operation] to ‘0’ (Enable
Logic), by using one of these methods:

An explicit message in the Logix program to write to the parameter.

A HIM or drive software tool to set the parameter.